14.2.4.1

Required settings at the master

For a "safe" data transfer, one controller must be the master in the network. The master controls and

synchronises the network.
Make the following two settings for the controller which is to be the master in the network:

• Axis bus address (

C02430/1

) = "1"

• With this setting, the controller automatically takes over the control in the network.
• Only one master is allowed in the network.

• Axis bus IO function (

C02440/1

) = "1: Master"

• With this setting, the controller outputs a synchronisation cycle to the I/O axis bus to which

the slaves can orient themselves.

Optional: Synchronisation of the internal time base of the master
For the master, a sync signal source (e.g. CAN or MCI) can be selected in

C01120

.

• Then, the entire axis bus system behaves synchronously with this sync signal.
• The sync signal source "2: AxisBusIO" technically does not make any sense for the axis bus

master and is thus ignored (same effect as with setting "0: Off").

Related topics:

"Master/slave" function

( 852)

Synchronisation of the internal time base

( 857)

14.2.4.2

Required settings for the slaves

Make the following settings for every slave controller in the network:

• Axis bus address (

C02430/1

) = "2" ... "62"

• Make sure that all controllers connected to the axis bus have different axis bus addresses.

• Sync signal source (

C01120

) = "2: AxisBusIO"

• With this setting, the synchronisation cycle output by the master is used as synchronisation

source.

• Basically, only one source is allowed to synchronise the internal time base.

• Axis bus IO function (

C02440/1

) = "2: Slave"

• This setting serves to define the slave.

Note!

The selection of the "2: AxisBusIO" sync signal source serves to permanently set the

parameters given in the following table for synchronising the internal time base to

reasonable values in order to ensure a technically perfect operation of the axis bus!

Parameter

Info

Setting for "AxisBusIO" signal source

Value Unit

C01121

Sync cycle time setpoint

2000 μs

C01122

Sync phase position

200 μs

C01123

Sync window

40 μs