3 activating the bus terminating resistor, Activating the bus terminating resistor, 14 axis bus – Lenze 8400 TopLine User Manual
Page 840
Advertising
14
Axis bus
14.2
Data transfer axis bus
840
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.2.3
Activating the bus terminating resistor
The axis bus must be terminated between axis bus low (AL) and axis bus high (AH) at the first and
last physical node each by a resistor (120 Ω).
The 8400 controller is provided with an integrated bus terminating resistor, which can be activated
via the DIP switch labelled with "AB":
[14-3] Activation of the integrated bus terminating resistor
• OFF = bus terminating resistor is inactive
• ON = bus terminating resistor is active
R
R
CA
AB
OFF
ON
120
Ù
AG
AL
AH
X10
AS