Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

783

12

System bus "CAN on board"

12.8

Process data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.8.5

Monitoring of the RPDOs for data reception

For RPDO1 ... RPDO4 each, a monitoring time can be parameterised within which the RPDO must

arrive. If the RPDO is not received within the monitoring time or not with the configured sync, the

response parameterised for each RPDO takes place.

Short overview: Parameters for RPDO monitoring

12.8.6

Configuring exception handling of the CAN PDOs

Exception handling for the CAN PDOs in the event of an error can be set via decoupling

configuration and decoupling values.

• Bit coded selection is carried out in

C00342/1

for the process data words read by the bus,

defining the events that will trigger decoupling.

• Bit coded selection is carried out in

C00342/2

for the process data words output by the

application, defining the events that will trigger decoupling.

Parameter

Info

Lenze setting

Value Unit

C00357/1...4

CAN1...4_IN monitoring time

3000 ms

C00593/1...4

Resp. to CAN1...4_IN monitoring

No response

Bit

Event

Bit 0  BusOff_MsgErr
Bit 1  Warning
Bit 2  NodeStopped
Bit 3  HeartBeatEvent
Bit 4  CAN1_In_Überw.
Bit 5  CAN2_In_Überw.
Bit 6  CAN3_In_Überw.
Bit 7  CAN4_In_Überw.
Bit 8 

Reserved

Bit 9 

Reserved

Bit 10 

Reserved

Bit 11 

Reserved

Bit 12 

Reserved

Bit 13 

Reserved

Bit 14  Trouble
Bit 15  Fault