Parameter list | C00105

910

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00105

C00106

C00107

Parameter | Name:

C00105 | Decel. time - quick stop

Data type: UNSIGNED_32

Index: 24470

d

= 5F96

h

The set deceleration time determines the ramp slope at quick stop

Activate/deactivate quick stop

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.900 2.000 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00106 | Auto DCB: Hold time

Data type: UNSIGNED_32

Index: 24469

d

= 5F95

h

Hold time of the automatic DC injection brake

• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in

C00019

.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.000 0.500 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00107 | DC braking: Hold time

Data type: UNSIGNED_32

Index: 24468

d

= 5F94

h

Maximum hold time of the manual DC injection brake

• A time can be set here after which the DC injection brake is switched off automatically to prevent the motor from

thermal overload.

• When "999.000 s" is set, the hold time is infinite.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.000 999.000 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000