19.1.106.6 Fine adjustment of the mains failure control

For the fine adjustment, repeat the following points several times:

1. A final speed as low as possible has to be reached before the controller reaches the operating

threshold for undervoltage (LU):

• Increase proportional gain Vp in

C01469/1

.

• Reduce Vdc-bus controller reset time in

C01470/1

.

2. The responding of the braking unit or the reaching of the operating threshold for overvoltage

(OU) has to be prevented:

• Increase Vdc controller reset time in

C01470/1

until the ideal profile shown in

[19-47]

will be

almost reached.

• If required, reduce the nDCSet_a voltage setpoint to which the DC-bus voltage is to be

controlled (in the interconnection example via the free parameter

C00476/2

).

3. Increasing the deceleration time or reducing the braking torque is only possible to a limited

extent:

• Increasing the acceleration time in

C01470/2

reduces the initial braking torque and

simultaneously increases the deceleration time.

• Increasing the Vdc controller reset time in

C01470/1

reduces the braking torque and

simultaneously increases the deceleration time. If the reset times are too high, the controller

reaches the operating threshold for undervoltage (LU) before standstill is reached. Hence, the

drive is not controlled anymore.

[19-48] Schematic diagram with different braking torques

n = speed of the drive

Operating threshold OU

Switch-on threshold - braking unit

Operating threshold - mains failure

Operating threshold LU

n

t

t

UG

0

1

2

3

t1

t2

t3

L_Compare_3.bOut

0

0

nDcSet_a

Point in time Info

t = t1

Mains failure

t = t2

Speed "0" with higher braking torque reached (short reset time).

t = t3

With a lower braking torque (higher reset time), the drive reaches the operating threshold for

undervoltage (LU) without reaching speed "0".

t > t3

Drive is not controlled anymore (is braked by friction).