C00018 | switching frequency, C00019 | auto dcb: threshold, C00018 – Lenze 8400 TopLine User Manual

Page 891: C00019, Ncy has to be set in, So that th, Are permiss, Ction in, Shold, 17 parameter reference

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

891

17

Parameter reference

17.2

Parameter list | C00018

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00018

C00019

Parameter | Name:

C00018 | Switching frequency

Data type: UNSIGNED_8

Index: 24557

d

= 5FED

h

Selection of the pulse width modulated switching frequency transferred from the inverter to the motor

• Select between an ideal setting for the drive which provides smooth running, and an optimal setting with regard

to the inverter which keeps its losses to a minimum (min. Pv).

• Both possibilities offer fixed and variable switching frequencies.

• When a variable switching frequency is selected, the switching frequency may change as a function of the load

and rotational frequency.

Selection of switching frequency

Selection list

(Lenze setting printed in bold)

1 4 kHz var./drive-optimised
2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised

11 4 kHz var./min. Pv
12 8 kHz var./min. Pv
13 16 kHz var./min. Pv
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv
21 8 kHz var./drive-opt./4 kHz min
22 16 kHz var./drive-opt./4 kHz min
23 16 kHz var./drive-opt./8 kHz min
31 8 kHz var./min. Pv/4 kHz min
32 16 kHz var./min. Pv/4 kHz min
33 16 kHz var./min. Pv/8 kHz min

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00019 | Auto DCB: Threshold

Data type: UNSIGNED_16

Index: 24556

d

= 5FEC

h

Setpoint speed threshold for automatic DC injection braking

• For speed setpoints with values below the thresholds a DC current is injected or the motor is not supplied with

current, depending on the setting.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0

rpm

60000 3 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1