17

Parameter reference

17.2

Parameter list | C00064

900

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00064

C00065

C00066

Parameter | Name:

C00064 | Device utilisation (Ixt)

Data type: INTEGER_16

Index: 24511

d

= 5FBF

h

Display of the device utilisation Ixt in different time resolutions

• If the value displayed here exceeds the threshold set in

C00123

, the fault message "OC5: Device overload (Ixt)"

is output and the fault response set in

C00604

is executed (default setting: "Warning").

Display range

(min. value | unit | max. value)

0.00

%

250.00

Subcodes

Info

C00064/1

Device utilisation (Ixt)

• Maximum value of the pulse utilisation (C00064/2)

and permanent utilisation (C00064/3).

C00064/2

Device utilisation (Ixt) 15s

• Pulse utilisation over the last 15 seconds (only for

loads >160 %).

C00064/3

Device utilisation (Ixt) 3 min

• Permanent utilisation over the last 3 minutes.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00065 | Supply voltage 24V

Data type: INTEGER_16

Index: 24510

d

= 5FBE

h

Display of the 24V supply voltage for the supply of the control electronics

Note:

The 24 V supply for the control electronics is either provided by an external supply or by the controller itself if it is

connected to the mains voltage.
Display range

(min. value | unit | max. value)

0.0

V

3276.7

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00066 | Thermal motor load (I²xt)

Data type: INTEGER_16

Index: 24509

d

= 5FBD

h

Display of the thermal motor load, sensorlessly determined using a motor model

• If the value displayed here exceeds "100.00 %", the error message "OC6: Thermal motor overload (I2xt)" is output

and the fault response set in

C00606

is executed (default setting: "Warning").

Motor overload monitoring (I2xt)

Display range

(min. value | unit | max. value)

0.00

%

199.99

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100