C01350 | acdrive: drive mode, C01351 | acdrive: control word, C01351/1 – Lenze 8400 TopLine User Manual

Page 1203: C01350/1, 17 parameter reference

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

1203

17

Parameter reference

17.2

Parameter list | C01350

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01350

C01351

Parameter | Name:

C01350 | ACDrive: Drive mode

Data type: UNSIGNED_8

Index: 23225

d

= 5AB9

h

Selection list

1 Speed mode
3 Torque mode

Subcodes

Lenze setting

Info

C01350/1

1: Speed mode

ACDrive: Drive mode

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01351 | ACDrive: Control word

Data type: UNSIGNED_16

Index: 23224

d

= 5AB8

h

From version 13.00.00

Display of the "AC Drive Profile" control word for the controller

• Detailed information on the "AC Drive Profile" can be found in the EtherNet/IP™ communication manual.

Actuating drive speed (AC Drive Profile)

Display area

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 Run Forward

Relationships between Run1 and Run2 and trigger

events can be found in the chapter "

Run/Stop Event

".

Bit 1 Run Backward
Bit 2 Fault Reset

0->1 ≡ Reset error

0 ≡ No response

Bit 3

Reserved

Bit 4

Reserved

Bit 5 NetCtrl

Run/Stop control:

0 ≡ via local setting in the device or terminal

1 ≡ via fieldbus (e.g. by the scanner)

Bit 6 NetRef

Reference speed/reference torque:

0 ≡ via local setting in the device or terminal

1 ≡ via fieldbus (e.g. by the scanner)

Bit 7

Reserved

Bit 8

Reserved

Bit 9

Reserved

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15

Reserved

Subcodes

Info

C01351/1

ACDrive: Control word

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT