Optimising the behaviour of the asynchronous motor, In the field weakening range, 5motor control (mctrl) – Lenze 8400 TopLine User Manual

Page 250

Advertising
background image

5

Motor control (MCTRL)

5.9

Servo control (SC)

250

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.9.4.8

Optimising the behaviour of the asynchronous motor in the field weakening range

The behaviour of the asynchronous motor in the field weakening range is influenced by:

• the field controller
• the field weakening controller
• the field feedforward control unit
• adaptive adaptation of the P component of the field and speed controllers
• An additional limitation of the I component of the controller when the voltage limit is reached

Note!

By default, these control parts are called every 1 ms. However, the 1-ms cycle is not

always sufficient to achieve an optimum jerk-free transition to the field weakening

range.

From version 14.00.00

, the control parts can be called for an optimum jerk-free

transition to the field weakening range in a 500-

μ

s cycle. For this purpose, bit 5 has to be

set to "1" int in

C02864/1

.

• With this setting,

C00015

and

C00576

do not have any influence anymore on the field

feedforward control.

• We recommend this setting for new applications.
• In existing applications, this setting may require an increase of the reset times of the

field weakening controller (

C00578

) and the field controller (

C00078

) by the factor 2

in order to achieve a stable operation.

In general, these settings are pre-optimised so that further optimisation is not required.
Optimisation for special motors (e.g. mid-frequency motors) or for standard

asynchronous motors whose power is not adapted can be carried out according to the

algorithms shown in the following sections.

Advertising