19.1.71

L_Curve_1

This FB can optionally display a characteristic function or a curve function y=f(x), the X axis being

the input signal and the Y axis being the output signal.

• A limitation of the input value can be set in

C00961/1

(upper limit) and

C00961/2

(lower limit).

• The output value is internally limited to ±199.99 %. If a limitation of the output value is active,

bLimit is set to TRUE.

Inputs

Outputs

Parameter

Identifier

Data type

Information/possible settings

nIn_a

INT

Input value (x)

• ±16384 ≡ ±100 %

• A limitation of the input value can be set in C00961/1 (upper limit) and C00961/2

(lower limit).

Identifier

Data type

Value/meaning

nOut_a

INT

Output value (y)

• ±16384 ≡ ±100 %

• Internal limitation to ±32767 (±199.99 %)

bLimit

BOOL

"Limitation active" status signal

TRUE The output value is limited to ±199.99 %.

Parameter

Possible settings

Info

C00959/1

From version 02.00.00

-199.99

%

199.99 Output value

• Read only

C00960/1

Function selection

0 Out = 0

FB deactivated (Lenze setting)

1 Out = In
2 Out = f(In)

In preparation!

3 Out = f(table)

Function 3: nOut_a = f(table)

C00961/1

-199.99

%

199.99 Upper limit for input value

• Lenze setting: 199.99 %

C00961/2

-199.99

%

199.99 Lower limit for input value

• Lenze setting: -199.99 %