Encoder/feedback system

6.3

Multi-Encoder (X8)

334

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.2.4

Notes on evaluating absolute value encoder of SEL37 and SELxx types by SICK

For version 02.xx.xx the following applies:

• The 8400 TopLine controller recognises these encoder types, but sporadically reports the error

"

Sd4: open circuit MultiEncoder

" error if the open-circuit monitoring is activated in

C00603/1

(Lenze setting).

• The reason for this is a faulty open-circuit monitoring during the initialisation of the

controller.

• The error can be acknowledged so that the controller is able to start correctly.

• Moreover, the initialisation time of the encoder is critical. This is the time needed internally by

the encoder to respond to a read request of the controller.

• The maximum initialisation time in the controller is permanently set to 5.2 s. Depending on

the encoder used, it may be possible that this time is not sufficient (see data sheet for the

encoder manufacturer)!

• If the monitoring (e.g. die open-circuit monitoring) triggers with the "Fault" error response due

to an encoder error during operation, the position is not valid anymore in case of absolute value

encoders and must be reread from encoder.

• After the error message is reset, this does not take place automatically which may cause a

wrong position!

• Remedy: After the error message is reset with the SB

LS_ParReadWrite_1

, rewrite the code

C00422

and thus enforce a re-initialisation of the encoder. Then enable the application.

From version 12.00.00 the following applies:

• The initialisation time of the encoder is not critical anymore since the maximum initialisation

time can now be adjusted in

C00430/1

(to max. 20 seconds).

• During the set initialisation time, the controller remains in the "Init" device state and cannot

be enabled.

• The open-circuit monitoring is also suppressed during the set initialisation time so that the

error behaviour of the version 02.xx.xx is remedied as well.

• If the monitoring (e.g. die open-circuit monitoring) triggers with the "Fault" error response due

to an encoder error during operation, the position is not valid anymore in case of absolute value

encoders and must be reread from encoder.

• After the error message is reset, this takes place automatically.