C02593 | holding brake: activation time, C02593/1, C02593/2 – Lenze 8400 TopLine User Manual

Page 1272: 17 parameter reference

Advertising
background image

17

Parameter reference

17.2

Parameter list | C02593

1272

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02593

Parameter | Name:

C02593 | Holding brake: Activation time

Data type: UNSIGNED_32

Index: 21982

d

= 55DE

h

Time parameter for the delay of trigger signals of the holding brake control

Holding brake control

Setting range

(min. value | unit | max. value)

0.000

s

3600.000

Subcodes

Lenze setting

Info

C02593/1

0.000 s

Holding brake: Actual value monitoring

• Time in which the actual value is supposed to reach

the threshold for closing the brake if the setpoint has

already reached the threshold.

• Time > 0 s: If the actual speed value has not reached

the threshold within the time for brake application,

the holding brake is applied by control.

• Time = 0 s: The brake is only applied by control when

the actual speed has reached the application

threshold.

C02593/2

0.000 s

Holding brake: Application delay

• Time by which the control process for holding brake

application is delayed. The time expires when the

speed setpoint has reached the switching threshold

for application.

• With positioning processes, a continuous application

and release of the holding brake can thus be

suppressed for the set time.

C02593/3

0.000 s

Holding brake: Reserved

C02593/4

0.000 s

Holding brake: Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000