Axis bus

14.2

Data transfer axis bus

846

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

14.2.4.7

Axis bus data error monitoring

Operating mode
There are two error counters, one for incorrectly sent telegrams (

C02438/1

) and one for incorrectly

received telegrams (

C02438/2

).

• In an error-free normal operation, both error counters are = 0.
• Depending on the error type, the counters are increased by 8 in case of an error detection, and

reduced by 1 in case no error has occurred.

• If one of the two error counters is > 96, a warning is signalled via the LED AB-STATE (double

pulse).

• If an error counter increases or remains unchanged, a watchdog counter is increased in a 1-

ms cycle.

• If an error counter is reduced, the watchdog counter remains unchanged.
• If the error counters are = 0, the watchdog counter is reset to 0.

• If the watchdog counter reaches the monitoring time set in

C02431/3

:

• The error response set in

C00591/1

is activated (Lenze setting: "Fault").

• The error message "

Ab01: AchsbusTimeOut

" is entered into the logbook.

Parameterisation notes for "electrical shaft" application
When an "electrical shaft" is operated via an axis bus or generally via a bus system, data transfer

errors may occur due to e.g. EMC interferences. In order to prevent a mechanical offset of the drives

in case of a short-time interference only, the

L_Interpolator_1

function block should be used in the

slave drives. This function block has an internal correction mechanism which provides for an

automatic offset correction in case of a missing data telegram. The error monitoring can then be set

to an insensitive value (

C02431/3

= approx. 10 ... 30 ms) which results in a very robust transfer

system.

What happens in case of a cable break, loose contact or short circuit of the axis bus cable?
Such severe errors mostly cause a bus-off error in one or even several devices of the system.

• In this case as well, the data error monitoring is triggered.
• The "BusOff" state will be automatically reset after the time set in

C02431/2

has expired if the

error cause has been removed. Then, the axis bus changes to normal operation again.