6.2

Resolver (X7)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2

Resolver (X7)

6.2.1

Parameterising the resolver

Danger!

• If the resolver is used as motor encoder:

Safe operation of the motor is no longer ensured in the event of an error!

• If servo control (SC) or V/f control (VFCplus + encoder) are used:

For safety reasons, always select "Fault" (Lenze setting) in

C00603 2

as a response for

the (open-circuit) monitoring of the resolver!

Note!

If a Lenze motor with resolver is used, the resolver is the only item that can be selected

as speed sensor in

C00495

. Further resolver parameter setting is not required.

Moreover, Lenze synchronous motors do not require a pole position identification (PLI)

as the resolvers of the Lenze synchronous motors are pre-adjusted.

Note!

Acceptance of the resolver pole position from a Servo Drive 9400
The resolver pole position (

C00926/1

) cannot be simply accepted from a Servo Drive

9400 if the pole position (C58/1) considerably differs from -90 ° in the Servo Drive 9400.

• We always recommend a

pole position identification (PLI)

.

( 358)

• As an alternative, the following conversion has to be carried out for a transfer of the

resolver pole position from a Servo Drive 9400 to the 8400 TopLine:

Pole position

8400

(

C00926/1

) = - (pole position

9400_C58/1

+ 180 °)