4 evaluation of the output signal, 5 comparison function "actual value = setpoint, 4 evaluation of the output signal 1 – Lenze 8400 TopLine User Manual

Page 1611: 5 comparison function "actual value = setpoint" 1, 19 function library

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

1611

19

Function library

19.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

19.1.138.4 Evaluation of the output signal

After the limitation, the output signal is evaluated with the influencing factor nInfluence_a. The

evaluation is activated/suppressed along a ramp when the bEnableInfluenceRamp input is set to

TRUE. The ramp times are set with the parameters "Influence acceleration time" (

C00243

) and

"Influence deceleration time" (

C00244

).

19.1.138.5 Comparison function "Actual value = setpoint"

If setpoint and actual value are identical and there is no system deviation, the bSetEqAct status

output is set to TRUE.

• The hysteresis of the comparison function has a fixed value of 1 %.
• The symmetrical window around the setpoint for the comparison function can be set in

C00247

(Lenze setting: 2 %).

[19-61] Comparison function: Switching performance

[19-62] Comparison function: Example

Hysteresis (1 %, fixed value)

C00247

: Window

TRUE

FALSE

bSetEqAct

Set value

Act value

Œ 

Œ



Hysteresis (1 %, fixed value)

C00247

: Window

Act value

Set value

TRUE

FALSE

bSetEqAct

t

t

Œ





Œ