19.1.141.3 Calculation of the output signal

The output value at dnOut_p can be detected according to the following formula:

Example
You want to determine the counter content of the integrator at a certain speed at the input and a

certain integration time t.
Given values:

nIn_v = 1000 rpm ≈ integer value 1092
• Integration time t = 10 s
• Starting value of the integrator = 0

Solution:

• Conversion of the input signal at nIn_v:

• Calculation of the output value:

t = integration time

16384 ≡ 15000 rpm

1 ≡ 1 incr.

dnOut_p [incr.]

nIn_v [rpm] t [s] 65535 [incr./rev.]

=

1000 rpm

1000 rev.

60 s

-----------------------

=

dnOut_p

1000 rev.

60 s

-----------------------

10 s 65535 incr.

Rev.

----------------------------

10922666 incr.

=

=