19.1.141.3 Calculation of the output signal
The output value at dnOut_p can be detected according to the following formula:
Example
You want to determine the counter content of the integrator at a certain speed at the input and a
certain integration time t.
Given values:
• nIn_v = 1000 rpm ≈ integer value 1092
• Integration time t = 10 s
• Starting value of the integrator = 0
Solution:
• Conversion of the input signal at nIn_v:
• Calculation of the output value:
t = integration time
16384 ≡ 15000 rpm
1 ≡ 1 incr.
dnOut_p [incr.]
nIn_v [rpm] t [s] 65535 [incr./rev.]
⋅
⋅
=
1000 rpm
1000 rev.
60 s
-----------------------
=
dnOut_p
1000 rev.
60 s
-----------------------
10 s 65535 incr.
Rev.
----------------------------
⋅
⋅
10922666 incr.
=
=