2 setting the baud rate, 3 setting the node address, Setting the baud rate – Lenze 8400 TopLine User Manual

Page 754: Setting the node address, 12 system bus "can on board

Advertising
background image

12

System bus "CAN on board"

12.2

Possible settings via DIP switch

754

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.2.2

Setting the baud rate

The baud rate can be set via code

C00351

or with the DIP switches a to c:

12.2.3

Setting the node address

The node address can be set via code

C00350

or with the DIP switches 1 to 64.

• The labelling on the housing corresponds to the values of the individual DIP switches for

determining the node address.

• The valid address range depends on the number of SDO channels set in

C00366

:

• 1 SDO (Lenze setting): 1 ... 127
• 2 SDO: 1 ... 63

Note!

• All DIP switches (a ... c, 1 ... 64) = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.

• Preset baud rate: 500 kbps

DIP switch position

Baud rate

c

b

A

ON

OFF

ON

20 kbps

OFF

ON

ON

50 kbps

OFF

ON

OFF

125 kbps

OFF

OFF

ON

250 kbps

OFF

OFF

OFF

500 kbps

ON

OFF

OFF

1000 kbps

Note!

• The addresses of the nodes must differ from each other.
• All DIP switches (a ... c, 1 ... 64) = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.