Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
643
9
Basic drive functions (MCK)
9.8
Positioning
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Note!
If disproportionately high S-ramp times are set for low acceleration times, this may
result in an incorrect profile generation.
Example: v = 100 mm/s, a = 1000 mm/s
2
t
acc
= 0.1 s
t
jerk_max
= 1 s
For this reason, you must only set plausible S-ramp times (this should not exceed half the
value of t
acc
).