Sd3: open circuit - feedback system [xx.0123.00205, Sd13: inaccuracy sincos [xx.0123.00206, An01: ain1_i < 4 ma [xx.0125.00001 – Lenze 8400 TopLine User Manual

Page 717: An02: ain2_i < 4 ma [xx.0125.00002, Sd3: open circuit - feedback system, Xx.0125.00001, Xx.0125.00002, Xx.0123.00205, Xx.0123.00206, 10 diagnostics & error management

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

717

10

Diagnostics & error management

10.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Sd3: Open circuit - feedback system [xx.0123.00205]

Sd13: Inaccuracy SinCos [xx.0123.00206]

An01: AIN1_I < 4 mA [xx.0125.00001]

An02: AIN2_I < 4 mA [xx.0125.00002]

Response (Lenze setting printed in bold)

Setting:

C00586

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

• HTL encoder cable interrupted.

• HTL encoder is defective.

Note: The reason can also be a very dynamic acceleration

or an approach against a blocked motor shaft, e.g. with a

a closed holding brake or when referencing to positive

stop (mode 14/15) and a waiting time (

C01223

)

>100 ms.

• Check HTL encoder cable.

• Check HTL encoder.

• Check related terminals.

• Switch off monitoring (

C00586

= "0: No reaction")

when the HTL encoder is not used.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Only in case of "Multi-Encoder" speed encoder selection

(

C00495

= 3):

A plausibility check for the digital and analog signals of

the absolute value encoder (Hiperface) or sin/cos

encoder has responded.

• The reason for this are EMC interferences.

• This information is given since angle errors (position

error) can occur in such a case.

Eliminate EMC interference.

Response (Lenze setting printed in bold)

Setting:

C00598/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Open-circuit monitoring for analog input 1 has tripped.

• Only if the analog input has been configured as a

current loop of 4 ... 20 mA (

C00034/1

= 2).

• Check wiring of the analog X3/A1I input terminal for

open circuit.

• Check minimum current values of the signal sources.

Response (Lenze setting printed in bold)

Setting:

C00598/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Open-circuit monitoring for analog input 2 has tripped.

• Only if the analog input has been configured as a

current loop of 4 ... 20 mA (

C00034/2

= 2).

• Check wiring of the analog X3/A2I input terminal for

open circuit.

• Check minimum current values of the signal sources.