17

Parameter reference

17.2

Parameter list | C00029

894

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00029

C00030

C00033

Parameter | Name:

C00029 | AINx: Input current

Data type: INTEGER_16

Index: 24546

d

= 5FE2

h

Display of the input current at the analog inputs

• When the corresponding analog input is configured for current measurement (

C00034/x

= 1 or 2).

• When

C00034/x

is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.

Analog terminals

Display range

(min. value | unit | max. value)

0.00

mA

20.00

Subcodes

Info

C00029/1

AIN1: Input current

C00029/2

AIN2: Input current

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00030 | LS_DFOut: Const.

Data type: INTEGER_16

Index: 24545

d

= 5FE1

h

From version 12.00.00

Settings for the digital frequency output (multi-encoder interface X8)

Digital frequency coupling

Setting range

(min. value | unit | max. value)

16

16384

Subcodes

Lenze setting

Info

C00030/1

2048

LS_DFOut

: number of increments

• The number of increments determines after how

many output increments a zero pulse will be

generated. Each zero pulse defines a covered

"revolution" of the rotary transducer simulated by the

digital frequency output.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00033 | AINx: Output value

Data type: INTEGER_16

Index: 24542

d

= 5FDE

h

Display of the output value in percent of the analog input amplifier

• 100 % ≡ 16384 ≡ +10 V / +20 mA

Analog terminals

Display range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Info

C00033/1

AIN1: Output value

C00033/2

AIN2: Output value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100