1 parameterising the encoder, Parameterising the encoder, 6encoder/feedback system – Lenze 8400 TopLine User Manual

Page 337

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

337

6

Encoder/feedback system

6.3

Multi-Encoder (X8)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3.3

SSI absolute value encoder with Stegmann-SSI protocol

All SSI encoders which use the Stegmann SSI protocol are supported.

• Supported bit rates for SSI communication: 100 ... 1000 kbits
• Supported data word widths: 1 ... 31 bits (effective)
• Supported output code of the SSI encoder: Gray or binary
• The SSI encoder can be used as position encoder or master encoder with a minimum cycle time

of 1 ms.

• The SSI encoder can be supplied via X8 up to a maximum voltage of 12 V and a maximum

current of 0.25 A.

• The received SSI data words are provided to the application via the

LS_MultiEncoder

system

block for further processing in the function block editor.

6.3.3.1

Parameterising the encoder

Parameterisation dialog (cutout)

Further parameterisation dialogs:

Scaling of position value

SSI configuration

Note!

For some SSi encoder types it is common that despite a high data transfer rate an slow

position detection (e.g. every 5, 10 or 20 ms) takes place. In this case, the position control,

working in a 1-ms cycle, only functions with low gain and thus low dynamics since the

values of the SSI encoder are only updated every x ms.
When an external SSI laser position encoder is used at X8:
Also observe the

Notes for using an SSI laser position encoder

at the end of this chapter.

( 341)

Parameter

Info

Lenze setting

Value Unit

C00422

LS_MultiEncoder: Encoder type

0: Incremental encoder (TTL)

C00421

LS_MultiEncoder: Supply voltage

5.0 V

C01112/1

LS_MultiEncoder: Position offset

0.0000 units

Advertising