Parameter reference

17.2

Parameter list | C02862

1284

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02862

C02863

C02864

Parameter | Name:

C02862 | Resolver gain

Data type: UNSIGNED_16

Index: 21713

d

= 54D1

h

Encoder/feedback system: Resolver

Setting range

(min. value | unit | max. value)

0.00

%

199.99

Subcodes

Lenze setting

Info

C02862/1

100.00 %

Resolver: sine gain

C02862/2

100.00 %

Resolver: cos gain

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C02863 | Resolver: Phase error

Data type: INTEGER_16

Index: 21712

d

= 54D0

h

Encoder/feedback system: Resolver

Setting range

(min. value | unit | max. value)

Lenze setting

-199.99

%

199.99 0.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C02864 | MCTRL: Optimisiations

Data type: UNSIGNED_16

Index: 21711

d

= 54CF

h

From version 14.00.00

Activation of special functions of the internal motor control
Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 Motor temp. 90° for operation

without KTY

1 ≡ Warm machine. In case the temperature tracking is

not active, a motor temperature of 90 °C is assumed.

Temperature compensation within the motor control

Bit 1 No switch-off of the brake chopper

after 4s

1 ≡ Limitation of the operating time of the brake chopper

(brake transistor) is deactivated.

Braking operation/brake energy management

Bit 2 Brake chopper off in case of trip

0 ≡ No response of the brake chopper in the "Fault"

device status.

1 ≡ In the "Fault" device status, the brake chopper is

permanently switched off without any delay.

Braking operation/brake energy management

Bit 3 Reserved (do not change!)
Bit 4 Motor ident: Switching frequency

8kHz

Switching frequency for motor parameter identification:

0 ≡ 4 kHz

1 ≡ 8 kHz

Preventing a decrease of the switching frequency

Bit 5 Field/field weakening control in

500us

Cycle time for field weakening control:

0 ≡ 1 ms

1 ≡ 500 μs

Optimising the behaviour of the asynchronous motor

in the field weakening range