Device control (DCTRL)

4.2

Device state machine and device states

116

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.3

Ident

The controller has been provided with functions for automatically detecting the motor parameters,

the resolver error and the pole position of a synchronous motor. If such an "identification" is active,

the controller is in the "Ident" status.
The "Ident" device status can only be reached from the "

SwitchedOn

" device status, i.e. the

controller must be inhibited first so that identification can be started afterwards via the

corresponding device command:

After the identification is completed, the status changes back to "

SwitchedOn

".

"DRV-RDY" LED

"DRV-ERR" LED

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

Ident

0

0

1

0

Device command

Function

Detailed information

C00002/23

Motor parameter identification

Automatic motor parameter identification

C00002/25

Identify resolver error

e

Optimise resolver behaviour

C00002/34

Identify pole position (360°)

Pole position identification

Stop!

During the identification of the motor parameters or the pole position, the controller

does not respond to setpoint changes or control processes (e.g. speed setpoints, quick

stop, torque limitations).
While an identification is being executed,

• the application remains active,
• all system interfaces (IO, bus systems, etc.) remain active,
• error monitoring remains active,
• the inverter is controlled independently of the setpoint sources.