Motor control (MCTRL)

5.1

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Automatic calculation of the field weakening controller parameters for ASM servo control

From version 15.00.00

, the field weakening controller parameters are automatically calculated as

well after a successful motor parameter identification. Moreover, the special functions of the

internal motor control listed in the table are activated.

• If these parameters are not to be calculated/activated, bit 6 has to be set to "1" in

C02864/1

.

Principal sequence of the motor parameter identification

1. The motor stator resistance (

C00084

) is measured.

2. The inverter error characteristic is measured.
3. The motor stator leakage inductance (

C00085

) is measured.

4. The V/f base frequency (

C00015

) is calculated.

5. The slip compensation (

C00021

) is calculated.

6. The V

min

boost (

C00016

) is detected.

7. Only for asynchronous motors:

The motor magnetising inductance (

C00092

) and the motor rotor resistance (

C00082

) are

measured.
The motor magnetising current (

C00095

) is measured.

From version 12.00.00:

8. If

C02865/1

- bit 4 = "0" (Lenze setting):

The current controller and field controller parameters are calculated. (See

table

.)

9. If

C02865/1

- bit 5 = "1":

The speed controller parameters are calculated. (See

table

.)

10. If

C02865/1

- bit 6 = "1":

Other controller parameters are calculated. (See

table

.)

From version 15.00.00:

11. If

C02864/1

- bit 6 = "0" (Lenze setting):

The field weakening controller parameters are calculated and certain special functions of the

internal motor control are activated. (See

table

.)

Parameter

Info

ASM

PSM

C00577

SC: Vp field weakening controller

C00578

SC: Tn field weakening controller

Activation of special functions of the internal motor control

C02864/1

Bit 5 is set to "1"

Field/field weakening controllers are called in a 500-μs cycle.*

Bit 7 is set to "1"

In case of servo control for asynchronous motors, the rated motor

speed (

C00087

) is assumed for the calculation of the slip from the

nameplate (

C02879

/bit 1 = "0".*

Slip calculation from motor equivalent circuit diagram data

( 246)

* If bit 6 is set to "1" in

C02864/1

, bit 5 and bit 7 are reset to "0".