Encoder/feedback system

314

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6

Encoder/feedback system

The 8400 TopLine uses various encoder/feedback systems for the motor controls with speed

feedback and the position control:

• Resolver at X7
• Multi-Encoder at X8

• Incremental TTL encoders
• Incremental SinCos encoders
• SinCos absolute value encoder with HIPERFACE® protocol
• SSI absolute value encoder with Stegmann-SSI protocol
• Digital frequency coupling

(from version 12.00.00)

• HTL encoder at the digital DI1/DI2 or DI6/DI7 input terminals

Danger!

• If the encoder/resolver is used as motor encoder:

Safe operation of the motor is no longer ensured in the event of an error!

• If servo control (SC) or V/f control (VFCplus + encoder) are used: For safety reasons,

always select "Fault" (Lenze setting) in the following parameters as a response for the

(open-circuit) monitoring of the encoder!

C00586

: Resp. open circuit HTL encoder

C00603/1

: Resp. open circuit MultiEncoder

C00603/2

: Resp. open circuit resolver

• If an HTL encoder is used at the digital input terminals:

Observe the maximum input frequencies of the digital inputs!

• DI1/DI2: max. 200 kHz
• DI6/DI7: max. 10 kHz

• To avoid interference when using an encoder, only use shielded motor and encoder

cables!

Note!

Speed feedback is essential for the following motor control modes with feedback:

Servo control (SC)

V/f control (VFCplus + encoder)