C00081

C00082

C00083

C00084

C00085

Parameter | Name:

C00081 | Rated motor power

Data type: UNSIGNED_16

Index: 24494

d

= 5FAE

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.

Note:

It is mandatory to give the rated motor power for the sensorless vector control (

SLVC

) and the servo control (

SC

).

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

kW

500.00 11.00 kW

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00082 | Motor rotor resistance

Data type: UNSIGNED_32

Index: 24493

d

= 5FAD

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0

mOhm

200000 276 mOhm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00083 | Motor rotor time constant

Data type: UNSIGNED_16

Index: 24492

d

= 5FAC

h

Display of the rotor time constant of the motor

• This value is calculated from the rotor resistance and the rotor inductance (leakage and magnetising

inductance).

Display range

(min. value | unit | max. value)

0

ms

32767

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00084 | Motor stator resistance

Data type: UNSIGNED_32

Index: 24491

d

= 5FAB

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0

mOhm

200000 330 mOhm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00085 | Motor stator leakage inductance

Data type: UNSIGNED_16

Index: 24490

d

= 5FAA

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

mH

650.00 3.50 mH

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100