Ou: dc bus overvoltage [xx.0123.00014, Lu: dc bus undervoltage [xx.0123.00015, Oc1: power section - short circuit [xx.0123.00016 – Lenze 8400 TopLine User Manual

Page 709: Message, Lu: undervoltage in the dc bus, Lu: dc bus undervoltage, Xx.0123.00015, Xx.0123.00016, Xx.0123.00014, 10 diagnostics & error management

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

709

10

Diagnostics & error management

10.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oU: DC bus overvoltage [xx.0123.00014]

LU: DC bus undervoltage [xx.0123.00015]

oC1: Power section - short circuit [xx.0123.00016]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected an overvoltage in the DC bus. To

protect the device hardware, the inverter control is

switched off.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• If this error message remains active longer than the

time set in

C00601

, a "Fault" is tripped. Otherwise, the

deactivation of the error message causes the inverter

control to be enabled again

• In case of the control types VFCplus and SLVC, the

motor voltage is approached to the voltage

setpoint alongside a ramp.

From version 15.00.00

, this voltage ramp can be set

in

C00983/2

. If the described remedies are not

possible or do not have any effect, it may be

required to increase this voltage ramp as otherwise

an overcurrent interruption may be caused. This

only happens in case of high motor power and

mass inertia so that the Lenze setting of 1 s should

be sufficient in the majority of cases.

• Reduce load in generator mode.

• Use a brake resistor.

• Use a regenerative power supply unit.

• Establish a DC-bus connection.

• Select a braking method in

C00175

which stops the

ramp function generator when reaching the brake

chopper threshold ("HlgStop").

• In case of servo control (SC), set the speed controller

parameters correctly.

Response (Lenze setting printed in bold)

Setting:

C00600/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected a DC bus undervoltage. The

inverter control is switched off because the drive

properties of the motor control cannot be provided

anymore due to the DC bus undervoltage.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• Switch on mains supply or ensure sufficient supply via

DC bus.

• Adjust setting in

C00142

if required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised a short circuit of the motor

phases. To protect the device electronics, the inverter

control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If the device is inappropriately dimensioned with

regard to the motor load and the current limitation in

the controller (Imax controller) is set incorrectly, this

error message may also occur.

Motor control: Defining current limits

• Check motor connections and the corresponding plug

connector on the device.

• Only use permissible combinations of device power

and motor power.

• Do not set the dynamics of the current limitation

controller too high.