C02878 | kty motor temperature compensation, C02878, C02878/1 – Lenze 8400 TopLine User Manual

Page 1292: However, temperature, 17 parameter reference

Advertising
background image

17

Parameter reference

17.2

Parameter list | C02878

1292

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02878

Parameter | Name:

C02878 | KTY motor temperature compensation

Data type: UNSIGNED_16

Index: 21697

d

= 54C1

h

From version 02.00.00

A temperature compensation over the detected motor temperature (display in

C00063/1

) serves to compensate

inaccuracies in the output torque within the motor control in case of temperature changes of the asynchronous or

synchronous motor.

Note!

In the Lenze setting, the temperature compensation within the motor control is activated. The temperature

compensation, however, is only active with speed encoder selection "3: Multi encoder" or "4: Resolver" in

C00495

as

well as error-free KTY temperature detection (display in

C00063/1

≠ 255 °C).

Temperature compensation within the motor control

Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Bit 0 for SC PSM
Bit 1 for SC ASM
Bit 2

Reserved

Bit 3

Reserved

Bit 4

Reserved

Bit 5

Reserved

Bit 6

Reserved

Bit 7

Reserved

Bit 8

Reserved

Bit 9

Reserved

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15

Reserved

Subcodes

Lenze setting

Info

C02878/1

0x0003

KTY motor temperature compensation

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT