19.1.158.7 Action type "switching"

For switching digital output signals, 16 actions of "switching" type are available. Every action can set

two selectable bits of the wDigitalOutputs output signal to "0" or "1", independent of each other.

Action call (entry in the sequence table)

with action number xxx = 001 ... 016

Parameter
The available actions 1 ... 16 are represented via the subcodes 1 ... 16.

Parameter

Possible settings

Info

C01411/1...16

Switching act. n: Output switching A

• Selection of the sequencer output

which is to be set to the polarity

set in

C01412/x

.

0 Deactivated
1 Sequencer output 1

(Bit 0 of wDigitalOutputs)

2 Sequencer output 2

(Bit 1 of wDigitalOutputs)

... ...

16 Sequencer output 16

(Bit 15 of wDigitalOutputs)

C01412/1...16

Switching act. n: Pol. switching A

• State to which the sequencer

output selected in

C01411/x

is to

be set.

0 Set output bit to "0"
1 Set output bit to "1"

C01413/1...16

Switching act. n: Output switching B

• Selection of the sequencer output

which is to be set to the polarity

set in

C01414/x

.

0 Deactivated
1 Sequencer output 1

(Bit 0 of wDigitalOutputs)

2 Sequencer output 2

(Bit 1 of wDigitalOutputs)

... ...

16 Sequencer output 16

(Bit 15 of wDigitalOutputs)

C01414/1...16

Switching act. n: Pol. switching B

• State to which the sequencer

output selected in

C01413/x

is to

be set.

0 Set output bit to "0"
1 Set output bit to "1"

2 x x x