Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

291

5

Motor control (MCTRL)

5.12

Braking operation/brake energy management

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Fast discharge of the DC bus
The bBrakeChopperOn control input of the "brake chopper master" can be optionally used for a fast

discharge of the DC bus after the supply voltage has been switched off. The FB interconnection f the

"brake chopper master" has to be adapted so that the bBrakeChopperOn control input of the

SB

LS_MotorInterface

is connected to a digital bus or hardware signal (e.g. digital input on HIGH

level).

Note!

If the brake chopper master-slave operation is activated, plausibility monitoring is

carried out in the "brake chopper slaves":

• The brake transistor can only be switched on via the bBrakeChopperOn control signal

if the DC-bus voltage is greater than the brake chopper threshold minus 40 V

DC

.

• Exception: From a mains voltage of 513 V

AC

(or 725 V

DC

) and a mains voltage of 480

V or 500 V set in

C00173

, the plausibility monitoring is not effective anymore.

Note!

Only the brake transistor of the "brake chopper master" is switched on with this function

(max. 4 seconds, without interruption).
A complete discharge of the DC-bus cannot be achieved using this function!

From version 14.00.00

, the limitation of the operating time can be deactivated to max. 4

seconds. For this purpose, set bit 1 to "1" in

C02864/1

.

• We recommend this setting when this function is used in order to achieve a higher

discharge of the DC bus - especially in case of high device power.