C00130 | rated power - brake resistor, C00131 | rated heat amount of brake resist, C00133 | brake resistor utilisation – Lenze 8400 TopLine User Manual

Page 914: C00134 | l_nset_1: ramp smoothing, C00133, C00130, C00131, C00134, 17 parameter reference

Advertising
background image

17

Parameter reference

17.2

Parameter list | C00130

914

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00130

C00131

C00133

C00134

Parameter | Name:

C00130 | Rated power - brake resistor

Data type: UNSIGNED_16

Index: 24445

d

= 5F7D

h

Rated power of the connected brake resistor

• The value to be entered can be obtained from the nameplate of the brake resistor.

Setting range

(min. value | unit | max. value)

Lenze setting

0

W

65535 100 W

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00131 | Rated heat amount of brake resist.

Data type: UNSIGNED_16

Index: 24444

d

= 5F7C

h

Thermal capacity of the connected brake resistor

• The value to be entered can be obtained from the nameplate of the brake resistor.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

kWs

6553.5 10.0 kWs

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00133 | Brake resistor utilisation

Data type: UNSIGNED_16

Index: 24442

d

= 5F7A

h

Display of the utilisation of the connected brake resistor
Display range

(min. value | unit | max. value)

0

%

65535

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00134 | L_NSet_1: Ramp smoothing

Data type: UNSIGNED_8

Index: 24441

d

= 5F79

h

The

L_NSet_1

FB: Configuration of the ramp rounding for the main setpoint

Selection list

(Lenze setting printed in bold)

Info

0 Off

Ramp rounding deactivated

1 PT1 behaviour

Ramp rounding with PT1 behaviour

• The corresponding S-ramp time must be set in

C00182

.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1