C00020 | ain2: characteristic, C00021 | slip comp, C00022 | imax in motor mode – Lenze 8400 TopLine User Manual

Page 892: C00023 | imax in generator mode, C00022, C00021, Mpensation, C00023, Motor mode, For generator load set in

Advertising
background image

17

Parameter reference

17.2

Parameter list | C00020

892

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00020

C00021

C00022

C00023

Parameter | Name:

C00020 | AIN2: Characteristic

Data type: INTEGER_16

Index: 24555

d

= 5FEB

h

Analog terminals

:

Signal adaptation via characteristic

Setting range

(min. value | unit | max. value)

0.00

%

199.99

Subcodes

Lenze setting

Info

C00020/1

0.00 %

AIN2: (+y0) = min

C00020/2

0.00 %

AIN2: (+x0) = Dead band

C00020/3

0.00 %

AIN2: (-y0) = (-min)

C00020/4

0.00 %

AIN2: (-x0) = (-Dead band)

C00020/5

100.00 %

AIN2: (+ymax)

C00020/6

100.00 %

AIN2: (+xmax)

C00020/7

100.00 %

AIN2: (-ymax)

C00020/8

100.00 %

AIN2: (-xmax)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00021 | Slip comp.

Data type: INTEGER_16

Index: 24554

d

= 5FEA

h

Slip compensation for V/f characteristic control (

VFCplus

) and sensorless vector control (

SLVC

)

• A higher slip compensation results in a higher increase in frequency and voltage when the machine is under load.

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.

Motor control (MCTRL)

:

Optimising the operational performance by slip compensation

Setting range

(min. value | unit | max. value)

Lenze setting

-100.00

%

100.00 2.67 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00022 | Imax in motor mode

Data type: UNSIGNED_16

Index: 24553

d

= 5FE9

h

Maximum current in motor mode for all motor control modes
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

655.35 47.00 A

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00023 | Imax in generator mode

Data type: INTEGER_16

Index: 24552

d

= 5FE8

h

Maximum current in generator mode for all motor control modes

• 100 % ≡ Imax in motor mode (

C00022

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 100.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Advertising