Parameter list | C00034

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00034

C00036

Parameter | Name:

C00034 | AINx: Configuration

Data type: UNSIGNED_8

Index: 24541

d

= 5FDD

h

Configuration of the analog inputs for current or voltage measurement

Analog terminals

Selection list

Info

0 -10V..+10V

Input signal is the voltage signal -10 V ... +10 V

• -10 V ... +10 V ≡ -100 % ... +100 %

1 0mA..20mA

Input signal is the current signal 0 mA ... 20 mA

• 0 mA ... 20 mA ≡ 0 % ... +100 %

2 4mA..20mA

Input signal is the current signal 4 mA ... 20 mA

• 4 mA ... 20 mA ≡ 0 % ... +100 %

• The current loop is monitored for open circuit

(I < 4 mA) by the device.

Subcodes

Lenze setting

Info

C00034/1

0: -10V..+10V

AIN1: Config.

C00034/2

0: -10V..+10V

AIN2: Config.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00036 | DC braking: Current

Data type: INTEGER_16

Index: 24539

d

= 5FDB

h

Braking current in [%] based on rated device current (

C00098

)

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

200.00 50.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100