Oc2: power section - earth fault [xx.0123.00017, Sd2: open circuit resolver [xx.0123.00024, Sd7: encoder communication error [xx.0123.00026 – Lenze 8400 TopLine User Manual

Page 710: Sd4: open circuit multiencoder [xx.0123.00027, Sd7: error encoder communication, Sd7: encoder communication error, Sd4: open circuit multiencoder, Logbook entry, Sd2: open circuit - resolver, Sd4: open circuit - multiencoder

Advertising
background image

10

Diagnostics & error management

10.9

Error messages of the operating system

710

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oC2: Power section - earth fault [xx.0123.00017]

Sd2: Open circuit resolver [xx.0123.00024]

Sd7: Encoder communication error [xx.0123.00026]

Sd4: Open circuit MultiEncoder [xx.0123.00027]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised an earth fault at one of the

motor phases. To protect the device electronics, the

inverter control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If motor filter, motor cable length, and cable type

(shielding capacity) are dimensioned incorrectly, this

error message may occur due to leakage currents to

PE.

• If motor filters with additional terminals for +UG and

–UG and devices greater or equal 3 kW are used, the

earth fault detection may be triggered due to leakage

currents to +UG and –UG.

• A cause can also be the use of shielded motor cables

longer than 50 m.

• Check motor connections and the corresponding plug

connector on the device.

• Use motor filters, cable lengths, and cable types

recommended by Lenze.

• If motor filters with additional terminals for +UG and

–UG and devices greater or equal 3 kW are used:

• Deactivate earth-fault detection during operation

by setting the filter time (

C01770

) to 250 ms.

• If motor cables longer than 50 m are used:

• Increase filter time for earth-fault detection during

operation (

C01770

).

Response (Lenze setting printed in bold)

Setting:

C00603/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

• Encoder signal interferences (EMC).

• Resolver cable interrupted.

• Resolver defective.

• Check resolver cable.

• Check resolver.

• Switch off monitoring (

C00603/2

= "0: No reaction")

when the resolver is not used.

Response (Lenze setting printed in bold)

Setting:

C00603/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

• Encoder cable interrupted.

• Encoder defective.

• Check encoder cable

• Check encoder.

• Check parameter setting.

Response (Lenze setting printed in bold)

Setting:

C00603/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

• Encoder cable interrupted.

• Encoder defective.

• Supply voltage for the encoder not sufficient.

• Check encoder cable.

• Check encoder.

• Check the set encoder supply voltage in

C00421

.

Adapt setting to the max. permissible encoder supply

voltage. If required, additional voltage drops of the

encoder cable have to be taken into consideration.

• Switch off monitoring (

C00603/1

= "0: No reaction")

when the encoder is not used.