Definition of the blocking zones
The subcodes of codes

C00632

and

C00633

can be used to define three zones which are to be

skipped by the output setpoint and which are to be passed as fast as possible by the ramp function

generator.
The example below shows the parameter setting of two blocking zones:

[19-52] Zone masking by means of parameterisable blocking zones

• The parameterised blocking zones have the same effect on negative input signals.
• A blocking zone is deactivated by entering identical limit values (in our example: blocking zone

3).

Parameter

Blocking zone 1

Blocking zone 2

Blocking zone 3

Minimum limit value

C00633/1: 48 %

C00633/2: 138 %

C00633/3: 0 %

Maximum limit value

C00632/1: 104 %

C00632/2: 178 %

C00632/3: 0 %

Blocking zone 1

Blocking zone 2

Output [%]

Input [%]

1

0

199.99

-199.99

-199.99

199.99

C00632/1

C00633/1

48

138

0

1

104

178

C00632/2

C00633/2