Id8: speed encoder has not been set [xx.0123.00061, Sd8: encoder angular drift monit. [xx.0123.00062, Oc11: clamp operation active [xx.0123.00071 – Lenze 8400 TopLine User Manual

Page 713: Oc12, Oc12: i2xt brake resistor overload, Oc12: i2xt overload brake resistor, Sd8: encoder angular drift monit, Error m, Xx.0123.00060, Xx.0123.00061

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

713

10

Diagnostics & error management

10.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Id7: Motor control does not match motor data [xx.0123.00060]

Id8: Speed encoder has not been set [xx.0123.00061]

Sd8: Encoder angular drift monit. [xx.0123.00062]

oC12: I2xt overload - brake resistor [xx.0123.00065]

oC11: Clamp operation active [xx.0123.00071]

Response (Lenze setting printed in bold)

Setting:

C00571/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

At controller enable, the device has detected that the

motor control type set in

C00006

cannot control the

motor type set.

• Example: Motor nameplate data for an asynchronous

motor have been entered; however, a motor control

type for a synchronous motor is set in

C00006

.

Note:

Since the "VFCplus" control types are able to control

every motor to a certain extent, this error message will

never occur here.

Enter correct motor nameplate data and set a matching

motor control type in

C00006

:

• Motor nameplate data asynchronous motor  motor

control type must be ASM, SLVC or VFCplus servo

control.

• Motor nameplate data synchronous motor  motor

control type must be PSM, SLPSM or VFCplus servo

control.

Response (Lenze setting printed in bold)

Setting:

C00571/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

When being In controller enable status, the device has

detected that a motor control type with feedback has

beent set in

C00006

, but no speed sensor has been set in

C00495

.

Set the speed sensor in

C00495

.

Note: The error can only be reset if the settings in

C00006

and

C00495

match.

Response (Lenze setting printed in bold)

Setting:

C00603/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

• Encoder signal interferences (EMC).

• Encoder cable interrupted.

• Encoder defective.

• Faulty parameter setting of the encoder.

• Check encoder cable, use shorter encoder cable if

required.

• Check encoder.

• Check parameter setting.

• If required, switch off monitoring (

C00603/3

).

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Too frequent and too long braking processes.

Check drive dimensioning.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device indicates that the "CLAMP" overcurrent

limitation has been activated.

• A permanent clamp operation causes an overload

disconnection.

Reduce setpoint generation dynamics or motor load.