6 cause & possible remedies, Su02: one mains phase is missing [xx.0111.00002, Su03: too frequent mains switching [xx.0111.00003 – Lenze 8400 TopLine User Manual

Page 705: Cause & possible remedies, Su02, Su02: one mains phase is missing, Error message, Cause, Possible remedies, Xx.0111.00002

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

705

10

Diagnostics & error management

10.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.9.6

Cause & possible remedies

This chapter contains all error messages of the controller operating system in numerical order of the

error numbers. The list provides detailed information on the response to the error message as well

as information on the cause & possible remedies.

Tip!
A list of all error messages of the controller operating system in alphabetical order can be

found in the previous chapter "

Short overview (A-Z)

"

( 702)

.

Su02: One mains phase is missing [xx.0111.00002]

Su03: Too frequent mains switching [xx.0111.00003]

Note!

For the sake of legibility, the

Logbook

and

C00165

display the error number with the

following syntax:

[Error type].[Error subject area no.].[Error ID]
In this documentation, "xx", a wildcard, stands for the error type since it is configurable

for many error messages.

Response (Lenze setting printed in bold)

Setting:

C00565

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

One mains phase of a three-phase supply has failed.

Check mains connection (terminal X100).

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Too frequent mains switching of the power section.

• The device recognises if the power section is switched

on and off too frequently.

• To protect internal charging connections from

destruction, the device reports this error and prevents

the controller inhibit. All other functions are active.

Use of a power supply module in the DC-bus connection,

the DC terminals of which are connected downstream to

the charging connection for the voltage DC bus (e.g.

9400 from 45 kW).

The error must be acknowledged by mains switching.

The charging circuit can only cool down when the mains

is switched off.

• After switching the mains 3 times in one minute,

there must be a switching pause of 9 minutes.

• Cyclic mains switching every 3 minutes is permissible.

From version 12.00.00 onwards

, this power supply

module can be used in the DC-bus connection by

enabling it via

C02865

(bit 8).

Note:

For further configuration of devices in the DC-bus

connection with 8400, the DC terminals of which are

connected downstream to the charging connection for

the voltage DC bus (e.g. 9400 from 45 kW with 8400)

contact Lenze.