C01191 | ptc characteristic: temperature 1/2, C01192 | ptc characteristic: resistance 1/2, C01193 | motor temp. feedback system – Lenze 8400 TopLine User Manual

Page 1175: C01201 | mck: cycle, C01201/1, Hen the cycle, C01193, C01191/1, C01191/2, C01192/1

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

1175

17

Parameter reference

17.2

Parameter list | C01191

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01191

C01192

C01193

C01201

Parameter | Name:

C01191 | PTC characteristic: Temperature 1/2

Data type: UNSIGNED_8

Index: 23384

d

= 5B58

h

The spec. thermal sensor characteristic is selected through the setting

C01190

="1"

Encoder/feedback system: Motor temperature monitoring (KTY)

Setting range

(min. value | unit | max. value)

0

°C

255

Subcodes

Lenze setting

Info

C01191/1

100 °C

PTC characteristic: Temperature 1

C01191/2

150 °C

PTC characteristic: Temperature 2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01192 | PTC characteristic: Resistance 1/2

Data type: INTEGER_32

Index: 23383

d

= 5B57

h

The spec. thermal sensor characteristic is selected through the setting

C01190

="1"

Encoder/feedback system: Motor temperature monitoring (KTY)

Setting range

(min. value | unit | max. value)

0

Ohm

30000

Subcodes

Lenze setting

Info

C01192/1

1070 Ohms

PTC characteristic: Resistance 1

C01192/2

2225 Ohm

PTC characteristic: Resistance 2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01193 | Motor temp. feedback system

Data type: UNSIGNED_8

Index: 23382

d

= 5B56

h

Selection of the feedback system for monitoring the motor temperature

Encoder/feedback system: Motor temperature monitoring (KTY)

Selection list

(Lenze setting printed in bold)

0 Speed feedback
1 Resolver input
2 Encoder input
5 Res. and enc. parallel

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01201 | MCK: Cycle

Data type: INTEGER_32

Index: 23374

d

= 5B4E

h

Cycle for Modulo measuring system

• When the cycle is set to 0 units (Lenze setting), the traversing range is unlimited (classical measuring system).

Activation of the Modulo measuring system

Setting range

(min. value | unit | max. value)

0.0000

units

214748.3647

Subcodes

Lenze setting

Info

C01201/1

0.0000 units

MCK: Cycle

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10000