3 function 3: dnin1 < dnin2, Function 3: dnin1 < dnin2 6, 19 function library – Lenze 8400 TopLine User Manual

Page 1426

Advertising
background image

19

Function library

19.1

Function blocks

1426

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

19.1.31.3 Function 3: dnIn1 < dnIn2

This function serves, for instance, to implement the comparison "actual speed is lower than a limit

value" (n

act

< n

x

) for one direction of rotation.

[19-16] Function 3: Switching performance

Functional sequence

1. If the value at dnIn1_p falls below the value at dnIn2_p, bOut changes from FALSE to TRUE.
2. Only if the signal at dnIn1_p exceeds the value of dnIn2_p - hysteresis again, bOut changes back

from TRUE to FALSE.

[19-17] Function 3: Example

C001671

: Hysteresis

TRUE

FALSE

bOut

dnIn2_p

dnIn1_p

Œ

C001671

: Hysteresis

dnIn1_p

dnIn2_p

TRUE

FALSE

bOut

t

t

Œ

Advertising