Parameter | Name:

C00417 | Deactivate resolver error comp.

Data type: UNSIGNED_8

Index: 24158

d

= 5E5E

h

Encoder/feedback system: Resolver

Selection list

(Lenze setting printed in bold)

0 Resolver error comp. act.
1 Resolver error comp. deact.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00420 | Number of encoder increments

Data type: UNSIGNED_16

Index: 24155

d

= 5E5B

h

Indication of the encoder constant

Encoder/feedback system: Multi-Encoder

Setting range

(min. value | unit | max. value)

1

Incr./rev.

32767

Subcodes

Lenze setting

Info

C00420/1

128 incr./rev.

FreqIn12: Encoder increment

C00420/2

128 incr./rev.

FreqIn67: Encoder increment

C00420/3

512 incr./rev.

LS_MultiEncoder

: Encoder increment

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00421 | LS_MultiEncoder: Supply voltage

Data type: UNSIGNED_16

Index: 24154

d

= 5E5A

h

Stop!

Before connecting an encoder, make sure that the encoder supply voltage is set correctly!

If the set supply voltage exceeds the permissible supply voltage of the connected encoder, the encoder may be

destroyed!

Encoder/feedback system: Multi-Encoder

Setting range

(min. value | unit | max. value)

Lenze setting

5.0

V

12.0 5.0 V

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10