1 change function assignment, Change function assignment, Change function assignment ( 379) – Lenze 8400 TopLine User Manual

Page 379: 7i/o terminals

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

379

7

I/O terminals

7.1

Digital input terminals

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.1.1

Change function assignment

The internal processing function of the digital input terminals DI1/DI2 and DI6/DI7 can be

reconfigured in

C00115

if necessary. In this way, these input terminals can alternatively be used as

frequency or counting inputs in order to implement the following functions:

• Detection of the input frequency
• Detection and processing of two unipolar input frequencies to one bipolar frequency
• Counting of input pulses
• Evaluation of the speed feedback (HTL encoder) for the motor control (speed-controlled

operation)

You can find detailed information on the respective function assignment in the following

subchapters:

Using DI1(6) and DI2(7) as digital inputs

( 380)

Using DI1(6) and DI2(7) as frequency inputs

( 381)

Using DI1(6) as counting input

( 386)

C00115/1: Function assignment DI1 and DI2

C00115/2: Function assignment of DI6 and DI7

Function assignment

DI1 / DI6

DI2 / DI7

0 DI1(6)=In / DI2(7)=In

Digital input

Digital input

1 DI1(6)=FreqIn / DI2(7)=In

Frequency input

Digital input

2 DI1(6)&DI2(7)=FreqIn (2-track)

Frequency input (2-track)

3 DI1(6)=FreqIn / DI2(7)=direction

Frequency input

(speed)

Frequency input

(direction)

4 DI1(6)=CountIn / DI2(7)=In

Count input

Digital input

Note!

• In the Lenze setting of

C00115

, the digital input terminals DI1/DI2 and DI6/DI7 have

been configured as "normal" digital inputs.

• The digital input terminals DI3 ... DI5 are basically designed as "normal" digital inputs.
• Very high pulse frequencies can be measured at the DI1/DI2 and DI6/DI7 input

terminals if the latter have been configured as frequency or counting inputs in

C00115

. Scanning is then carried out within less than μs instead of the otherwise

usual scanning rate of 1 kHz (1 ms).