C00039 | fixed setpoint x (l_nset_1 n-fix), C00050 | mctrl: speed setpoint, C00051 | mctrl: actual speed value – Lenze 8400 TopLine User Manual

Page 896: C00051, C00039/1, C00039/2, C00039/3, Is used, E (display in, As well as th

Advertising
background image

17

Parameter reference

17.2

Parameter list | C00039

896

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00039

C00050

C00051

Parameter | Name:

C00039 | Fixed setpoint x (L_NSet_1 n-Fix)

Data type: INTEGER_16

Index: 24536

d

= 5FD8

h

The

L_NSet_1

FB: Fixed speed setpoints (JOG values) for the setpoint generator

Setting range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Lenze setting

Info

C00039/1

40.00 %

Fixed setpoint 1

C00039/2

60.00 %

Fixed setpoint 2

C00039/3

80.00 %

Fixed setpoint 3

C00039/4

0.00 %

Fixed setpoint 4

C00039/5

0.00 %

Fixed setpoint 5

C00039/6

0.00 %

Fixed setpoint 6

C00039/7

0.00 %

Fixed setpoint 7

C00039/8

0.00 %

Fixed setpoint 8

C00039/9

0.00 %

Fixed setpoint 9

C00039/10

0.00 %

Fixed setpoint 10

C00039/11

0.00 %

Fixed setpoint 11

C00039/12

0.00 %

Fixed setpoint 12

C00039/13

0.00 %

Fixed setpoint 13

C00039/14

0.00 %

Fixed setpoint 14

C00039/15

0.00 %

Fixed setpoint 15

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00050 | MCTRL: Speed setpoint

Data type: INTEGER_32

Index: 24525

d

= 5FCD

h

Display of the speed setpoint at the speed setpoint input of the motor control
Display range

(min. value | unit | max. value)

-120000

rpm

120000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00051 | MCTRL: Actual speed value

Data type: INTEGER_32

Index: 24524

d

= 5FCC

h

Display of the actual speed value of the motor shaft

Note:

The displayed value only corresponds to the real actual speed value of the motor shaft if an encoder is connected to

the motor and the evaluation of the feedback signal has been set correctly ("Closed loop" operation).

In case of operation without speed feedback, the signal is calculated from the motor control and thus may not

correspond to the real actual speed.
Display range

(min. value | unit | max. value)

-120000

rpm

120000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising