Encoder/feedback system

6.3

Multi-Encoder (X8)

332

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to parameterise a SinCos absolute value encoder with unknown type code:
If the encoder is not detected automatically, the value "0x00" is displayed in

C00492

as

TypeCode. In this case, make the settings manually:

1. Set the number of steps per revolution in

C00494/2

.

2. Set the number of revolutions for a multiturn encoder in

C00494/1

.

3. Set the number of sine/cosine periods per revolutions as "increment" of the encoder in

C00420/3

.

• This value can be obtained from the encoder data sheet.
• This point must be executed last since it initiates a renewed readout of the encoder.

4. If you use the encoder as motor encoder and synchronous motor of a third party

manufacturer:

Carry out

Pole position identification (PPI)

.

( 358)

5. For detecting and monitoring the motor temperature via the Encoder cable:

Parameterise

Motor temperature monitoring (KTY) via encoder

.

( 375)

6. Optional: Parameterise

Resolver/multi-encoder open-circuit monitoring

.

( 369)

In the Lenze setting, the resolver cable and/or encoder cable are monitored with regard to

open circuit as a function of the selected speed and position encoder.

7. For a permanent acceptance of the parameter settings:

Save parameter set.