Oh9: motor overtemperature resolver [xx.0119.00003, Oh3: motor temperature (x106) triggered, Error m – Lenze 8400 TopLine User Manual

Page 707: Oh9: motor overtemperature resolver, Oh6: motor temperature multiencoder > c121, Oh12: motor overtemperature multiencoder, Oh9: motor temperature - resolver, Sd6: thermal detector error - resolver, Oh6: motor temperature - multiencoder > c121, Oh12: motor overtemperature - multiencoder

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

707

10

Diagnostics & error management

10.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oH9: Motor overtemperature resolver [xx.0119.00003]

Sd6: Error thermal detector resolver [xx.0119.00012]

oH3: Motor temperature (X106) triggered [xx.0119.00015]

oH6: Motor temperature MultiEncoder >= C121 [xx.0119.00020]

oH12: Motor overtemperature MultiEncoder [xx.0119.00021]

Response (Lenze setting printed in bold)

Setting:

C00583/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The motor temperature detected via the resolver

interface has reached the fixed limit temperature

(150 °C).

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.

Response (Lenze setting printed in bold)

Setting:

C00583/5

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The signals of the encoder connected to the resolver

interface are outside the defined operating range of the

motor temperature detection.

• Check contacts of the encoder cable at the motor and

controller.

• Check the selected motor temperature sensor in

C01190/1

as to whether it complies with the

assembly in the motor.

• If required, switch off thermal sensor monitoring

(

C00583/5

="0").

Response (Lenze setting printed in bold)

Setting:

C00585

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The motor temperature monitoring function at the plug

connector X106, terminal T1 /T2, has tripped.

Possible causes:

• The motor is overheated so that the thermal contact

integrated into the motor has been switched.

• An open circuit or a loose contact at the connections

mentioned above has occurred.

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.

Response (Lenze setting printed in bold)

Setting:

C00583/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The motor temperature detected via the encoder

interface has reached the warning threshold set in

C00121/2

.

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.

Response (Lenze setting printed in bold)

Setting:

C00583/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The motor temperature detected via the encoder

interface has reached the fixed limit temperature

(150 °C).

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.