2 pole position identification without motion, Pole position identification without motion, Can be avoided – Lenze 8400 TopLine User Manual

Page 364: 6encoder/feedback system

Advertising
background image

6

Encoder/feedback system

6.5

Pole position identification (PPI)

364

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.5.2

Pole position identification without motion

This function extension is available from version 02.00.00!

From version 02.00.00, a pole position identification without motion is also possible in case of servo

control and sensorless control.

• For sensorless control of synchronous motors (SLPSM), this function is already activated in the

Lenze setting, i.e. with every controller enable the rotor displacement angle is identified and

thus jerks in the machine after controller enable can be avoided.

• In order to achieve the same behaviour as before, set bit 0 to "0" in

C02874

.

• For servo control (SC), this function can be activated for various events in

C02874

via the

bits 1 ... 3:

• Bit 1: Pole position identification after mains connection
• Bit 2: Pole position identification after controller enable
• Bit 3: Pole position identification after error acknowledgement

Tip!
In case of servo control (SC), it is generally sufficient to activate this function only once after

mains connection of the device (

C02874

: Bit 1 = "1").

Typical application case: A speed sensor with an unknown pole position is used (e.g.

encoder). The pole position identification 360°, however, cannot be used since, e.g. the

motor is locked, the application does not permit it or the identification takes too long.

Note!

Function only possible with:

Servo control (SC) for synchronous motors

Sensorless control for synchronous motors (SLPSM)

Note!

• The "Pole position identification without motion" cannot completely replace the "pole

position identification 360°"!

• The electrical rotor displacement angle can only be electrically identified with an

error of up to 10°. This inaccuracy can cause a worse torque accuracy and a worse

energy efficiency.

• The identification takes motor-dependent 1 ... 15 ms. The setpoint enabling of the

device is reduced by this time.

• In the Lenze setting, the function is preset so that in most of the cases no further

settings have to be made.