9 field weakening for synchronous motors, Field weakening for synchronous motors, 5motor control (mctrl) – Lenze 8400 TopLine User Manual

Page 276: Stop

Advertising
background image

5

Motor control (MCTRL)

5.10

Parameterisable additional functions

276

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.10.9

Field weakening for synchronous motors

This function extension is available from version 02.00.00!

[5-25] Voltage/speed characteristic with switched-on field weakening

[5-26] Calculation of the maximally reachable speed with switched-on field weakening

Note!

Function only possible with:

• Servo control (SC)
• Sensorless control for synchronous motors (SLPSM)

(from version 10.00.00)

In the Lenze setting, the field weakening for synchronous motors is activated in

C00079/4

.

• If a high energy efficiency is required, keep the field weakening switched off or restrict

the field weakening operation via

C00938

.

Stop!

In the field weakening operation, a current is injected into the synchronous motor even

in idle state which can rise to maximum current (

C00022

).

Ensure that this no-load current does not cause the motor to be heated impermissibly!

• The use of a temperature feedback via KTY is recommended.

Motor temperature

monitoring (KTY)

( 373)

Armature control range

Field weakening range

• When field weakening is switched on, the motor

magnetising current is increased from 0 A to the maximally

effective magnetising current via an internal control loop

when the voltage limit is reached.

• As a result, a higher speed can be reached at the same

motor voltage or DC-bus voltage.

n

Œ



U

motor

n

max

n

nenn_mot

800V

2 U

nenn_mot

--------------------------------------

=