14 axis bus – Lenze 8400 TopLine User Manual

Page 853

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

853

14

Axis bus

14.3

IO axis bus

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Error status
By setting the

LS_AxisBusIO

.bSetFail_DigOut input to TRUE, each node can set the IO axis bus into

the "Error" status. The node signalises this by reducing the HIGH pulse length to 620 μs:

[14-6] Synchronisation cycle (error status)

All other nodes detect the "error status" due to the changed pulse length which has the following

effect:

• The

LS_AxisBusIO

.bFail_DigIn output is set to TRUE. This digital signal can be used for any

application within the function block interconnection.

From version 12.00.00:

• The error response set in

C00591/2

is activated (Lenze setting: "Fault").

• The error message "

Ab02: Axis bus IO error

" is entered into the logbook.

• The nodes are now error-passive, i.e. they cannot signalise any further errors in order that the

HIGH edge for synchronisation can be detected after 2 ms.

Reset "error" status

A FALSE/TRUE edge at the

LS_AxisBusIO

.bResetFail input (for the master) serves to reset the "error"

status again. The master signalises this by providing a LOW pulse for 3 ms.
All other nodes detect the error reset due to this signal, which has the following effect:

• The

LS_AxisBusIO

.bFail_DigIn output is reset to FALSE.

• After a delay time of 2 ms, the

LS_AxisBusIO

.bResetFailIn output is set for 3 ms to TRUE. This

digital signal can be used within the function block interconnection to e.g. reset errors.

A node signalises "Error" by a reduced HIGH pulse length

"Error" status is active for all nodes

W

9

9

—V

—V

—V

—V

—V

—V

Note!

The "error" status can only be reset by the master!