17.2

Parameter list | C02866

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02866

Bit 9 Inverter characteristics inactive

From version 12.00.00

In case of very low-inductance motors (e.g. synchronous

motor with a rated frequency of 1000 Hz) the inverter

error characteristic needs to be switched off as otherwise

the current of the device might be switched off.

0 ≡ Inverter error characteristic is active

1 ≡ Inverter error characteristic is not active

Bit 10 SCPSM: Extrapolation - actual speed

value inactive

Bit 11 TopLine: Speed encoder signal cycle

500us

Bit 12 In case of QSP - nTorqueSetValue_a

active

From version 13.00.00

Bit 13 In case of QSP - nTorquexxxLimit_a

active

From version 13.00.00

Bit 14 Sensitivity of setpoint feedf. ctrl. 16

bits

From version 14.00.00

Bit 15 SC: Dead time of speed setpoint

500us

From version 14.00.00

Subcodes

Lenze setting

Info

C02865/1

0x0000

MCTRL

: Special settings

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C02865 | MCTRL: Special settings

Data type: UNSIGNED_16

Index: 21710

d

= 54CE

h

Parameter | Name:

C02866 | MCTRL: Special settings

Data type: UNSIGNED_8

Index: 21709

d

= 54CD

h

Activation of special functions of the internal motor control
Selection list

0 No
1 Yes

Subcodes

Lenze setting

Info

C02866/1

1: Yes

Motor ident.: Current controller par. from C075 C076

Automatic motor data identification

C02866/2

0: No

Motor phase error monitoring before operation

From version 02.00.00

Motor phase error monitoring before operation

C02866/3

0: No

Brake chopper DC-bus slave

From version 12.00.00

Control of multiple internal brake choppers in the DC-

bus system

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1