C01029

C01030

C01031

Parameter | Name:

C01029 | L_Curve_2: Table Y-values

Data type: INTEGER_16

Index: 23546

d

= 5BFA

h

From version 02.00.00

FB

L_Curve_2

: Y-value for characteristic function

Setting range

(min. value | unit | max. value)

-32767

32767

Subcodes

Lenze setting

Info

C01029/1

0

Y values 1 ... 32 for characteristic function

C01029/...
C01029/32

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01030 | L_Curve_3: Selected curve type

Data type: UNSIGNED_8

Index: 23545

d

= 5BF9

h

From version 02.00.00

FB

L_Curve_3

: Selected curve type

Selection list

Info

0 Out = 0
1 Out = In
2 Out = f(In)
3 Out = f(table)
4 Out = f(characteristic)

From version 12.00.00

Subcodes

Lenze setting

Info

C01030/1

1: Out = In

L_Curve_3

: Function

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01031 | L_Curve_3: Input limitation

Data type: INTEGER_16

Index: 23544

d

= 5BF8

h

From version 02.00.00

FB

L_Curve_3

: Upper and lower limit for input value

Setting range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Lenze setting

Info

C01031/1

199.99 %

L_Curve_3

: Max. input

C01031/2

-199.99 %

L_Curve_3

: Min. input

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100