Parameterise, Motor temperature monitoring (kty) via encoder, 6encoder/feedback system – Lenze 8400 TopLine User Manual

Page 375

Advertising
background image

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

375

6

Encoder/feedback system

6.7

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Motor temperature monitoring (KTY) via encoder
The sensor type has to be selected in

C01190/2

.

• If the winding temperature detected via the motor temperature sensor reaches the limit value

set in

C00121/2

(Lenze setting: 120 °):

• An advance warning in the form of the error response set in

C00583/4

is issued.

• The "

oH6: Motor temperature - MultiEncoder > C121

" error message is entered into the

logbook.

• If the fixed limit value of 150 °C is reached:

• The error response set in

C00583/2

is triggered.

• The "

oH12: Motor overtemperature - MultiEncoder

" error message is entered into the

logbook.

• If open circuit is detected for the motor temperature sensor:

• The error response set in

C00583/6

is triggered.

• The "

Sd12: Thermal detector error - MultiEncoder

" error message is entered into the logbook.

Specific characteristic for the motor temperature sensor
A specific characteristic can be defined and activated for the motor temperature sensor if required.

• The specific characteristic is defined on the basis of two grid points which must be set in

C01191

and

C01192

. Those two points define a line which is extrapolated to the right and to the left.

• The specific characteristic can be activated by selecting "1: Spec. characteristic" in

C01190/1

for

the resolver and in

C01190/2

for the encoder.

• In the Lenze setting, the specific characteristic is defined as follows:

[6-4]

Lenze setting of the specific characteristic

• Interpolation point

C01191/1

= 100 °C

C01192/1

= 1070 Ω

• Interpolation point

C01191/2

= 150 °C

C01192/2

= 2225 Ω

0

1070

2225

0

150

W

°C

100

Œ



Note!

If a motor is selected from the motor catalogue, parameters

C01190

,

C01191

, and

C01192

are overwritten!